Is thermal expansion making the T&P valve leak?

Fixable — but not by replacing the valve

The valve is working correctly. Water expands about 2% when you heat it. If a check valve, backflow preventer, or pressure-reducing valve seals your plumbing off from the street main, that extra volume has nowhere to go — pressure climbs until the T&P valve lifts near 150 psi and lets some out.

How to tell it's this

What to do

  1. Screw a pressure gauge onto an outside spigot. They cost about $12 at any hardware store.
  2. Read it before the heater has run. Under 80 psi is normal.
  3. Run a lot of hot water, wait for the heater to reheat, then read it again. A rise of 20 psi or more confirms thermal expansion.
  4. Have a plumber fit a thermal expansion tank on the cold inlet.
  5. Do not just replace the relief valve. A new valve will lift on exactly the same schedule, and you will have paid twice.

What it costs

With a plumber

Add a thermal-expansion tank

$200–$450

installed

Part only

If a pro is already on site

$40–$80

the part itself

Typical US ranges for 2026, not quotes. Labour is 30–50% of an installed price, so where you live moves these numbers more than anything else does. Get two or three local estimates.

If that's not it

Not sure which of these it is? Answer four questions — where it's leaking, tank or tankless, gas or electric, and how old it is — for a specific cause, a repair-or-replace call, and a cost.